Continuity

Test Current 8.5 mA 2-wire:

0.0 Ω ... 19.99 Ω / 0.1 Ω / ±(5 % of reading + 3 digits)

20 Ω ... 1999 Ω / 1 Ω / ±(5 % of reading + 3 digits)

Test Current 200 mA 2-wire:

0.00 Ω ... 19.99 Ω / 0.01 Ω / ±(3 % of reading + 3 digits)

20.0 Ω ... 199.9 Ω / 0.1 Ω / ±(5 % of reading)

200.0 Ω ... 1999 Ω / 1 Ω / ±(5 % of reading)

Rpe (RCD: No):

0.00 Ω ... 19.99 Ω / 0.01 Ω / ±(5 % of reading + 5 digits)

20.0 Ω ... 199.9 Ω / 0.1 Ω / ±(5 % of reading + 5 digits)

200 Ω ... 1999 Ω / 1 Ω / ±(5 % of reading + 5 digits)

Insulation Resistance

Test Voltage 50/100/250 V:

0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of reading + 3 digits)

20.0 MΩ ... 99.9 MΩ / 0.1 MΩ / ±(10 % of reading)

100.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±(20 % of reading)

Test Voltage 500 V:

0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of reading + 3 digits)

20.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±(5 % of reading)

200 MΩ ... 999 MΩ / 1 MΩ / ±(10 % of reading)

Test Voltage 1000 V:

0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of reading + 3 digits)

20.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±(5 % of reading)

Voltage (Um): 0 V ... 1200 V / 1 V / ±(3 % of reading + 3 digits)

RCD Test

RCD Uc (Contact Voltage):

0.0 V ... 19.9 V / 0.1 V / (-0 %/+15 %) of reading ± 10 digits

20.0 V ... 99.9 V / 0.1 V / (-0 %/+15 %) of reading

RCD (t) (Trip Time):

0.0 ms ... 40.0 ms / 0.1 ms / ±1 ms

40.1 ms ... 999.9 ms / 0.1 ms / ±3 ms

1000 ms ... 1999 ms / 1 ms / ±3 ms

2.00 s ... 10.00 s / 10 ms / ±10 ms

RCD I Ramp (Trip Current):

0.1 mA ... 1.10 A / (Range dependent) / ±10 %

Impedance

Zline (L-L, L-N) & Zloop (L-PE):

0.00 Ω ... 9.99 Ω / 0.01 Ω / ±(3 % of reading + 3 digits)

10.0 Ω ... 99.9 Ω / 0.1 Ω / ±(3 % of reading + 3 digits)

100 Ω ... 999 Ω / 1 Ω / ±(10 % of reading)

1.00 kΩ ... 9.99 kΩ / 10 Ω / ±(10 % of reading)

Zs RCD:

0.00 Ω ... 9.99 Ω / 0.01 Ω / ±(5 % of reading + 10 digits)

10.0 Ω ... 99.9 Ω / 0.1 Ω / ±(5 % of reading + 10 digits)

100 Ω ... 9.99 kΩ / 1 Ω ... 10 Ω / ±(10 % of reading)

Voltage & Frequency

Voltage: 0 V … 550 V / 1 V / ±(2 % of reading + 2 digits)

Frequency: 14.0 Hz ... 499.9 Hz / 0.1 Hz / ±(0.2 % of reading + 1 digit)

EARTH RESISTANCE

3-wire Method:

0.00 Ω ... 19.99 Ω / 0.01 Ω / ±(5 % of reading + 5 digits)

20.0 Ω ... 199.9 Ω / 0.1 Ω / ±(5 % of reading + 5 digits)

200.0 Ω ... 9999 Ω / 1 Ω / ±(5 % of reading + 5 digits)

General Data

Power Supply: 7.2 V (5200 mAh) Li-ion battery pack

Overvoltage Category: 600 V CAT III; 300 V CAT IV

Protection Class: Double insulation

COM Port: Bluetooth, USB Type-C

Display: 4.3 inch Colour TFT touch screen (480 x 272 pixels)

Weight: 1.35 kg

Dimensions (L x H x W): 272 x 152 x 70 mm


Standard set (ST)

• Instrument MI 3136 EurotestCOMBO XC

• 1x A 1014 Test probe, Black

• 1x A 1015 Test probe, Blue

• 1x A 1062 Test probe, Green

• 1x A 1013 Crocodile clip, Black

• 1x A 1310 Crocodile clip, Blue

• 1x A 1309 Crocodile clip, Green

• 1x A 1193 Test cable, BLK/GRN/BLU, 1.5m,

0.75mm2

• 1x A 1053 Test cable, 1.5m, 0.75mm2

• 1x A 1857 USB cable, Type C

• Calibration certificate

• Short instruction manual

• Instruction manual

• Metrel ES Manager BASIC Licence

• SW 1201 Metrel ES Manager (program installation)

Datasheet

Stay Updated with Offers

Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.

By subscribing, you agree to our Terms of Service and Privacy Policy.

Quick Support

Direct access to our certified experts